AMF Panel

AMF (Auto Main Failure) Panel is an automated electrical control system that acts as as bridge between the main utility power supply the "mains" and a backup generator. It is designed to automatically sense a power outage and switch the load to the generator without human intervention.

Technical Specifications

Feature 

Specification

Rated Voltage

415V AC

Frequency

50Hz | 60Hz

Rated Current

Upto 6300A

Short-Circuit Capacity

36kA to 50kA For 1s

Protection Class

IP54 | IP55 | IP65

Phase Configuration

3-Phase

Insulation Voltage

Up to 1000V

Busbars

Copper

Material

Mild Steel, Stainless Steel, Aluminium

Core Components

§  AMF Controller: 
A specialized microprocessor or PLC that manages the entire logic sequence.

§  Contactors/ACBs: 
High-power switching devices (mechanically or electrically interlocked) to prevent the mains and generator from connecting at the same time.

§  Battery Charger: 
An integrated charger that keeps the generator’s starting batteries at full capacity during standby.

§  Sensing Relays: 
Used to detect phase failure or voltage fluctuations. 

Primary Functions

§  Mains Monitoring: 
Continuously tracks utility voltage, frequency, and phase balance.

§  Auto-Start: 
If the mains power fails or falls below a specific threshold (e.g., undervoltage), the panel sends a signal to start the Diesel Generator (DG).

§  Load Transfer: 
Once the generator reaches the correct voltage and frequency, the panel switches the building's electrical load from the mains to the generator.

§  Auto-Restoration: 
When utility power is restored and stable, the panel switches the load back to the mains and initiates a "cool-down" period for the generator before shutting it down.

§  Protection: 
Monitors the health of both the mains and the generator, protecting against over-current, earth faults, and engine issues (low oil pressure, high coolant temperature).

Safety Features

§  Electrical Protection:
Over-current, short-circuit, earth fault, and reverse power protection.

§  Engine Protection:
Automatic shutdown on Low Oil Pressure (LOP), High Water Temperature (HWT), Over-speed, and Under-speed.

§  Emergency Stop:
Dedicated mushroom-head push button on the front fascia. 

Standard Tests

 

§  TTA (Totally Type Tested Assembly) IEC 61439-1&2

§  PTA (Partially Type Tested Assembly) IEC 60439

Brands

§  Novatric Export 

Common Applications

§  Industries & Manufacturing | Infrastructure & Utility | Commercial | Renewable Energy | Telecom | Textile | Cement Industries | Hospitals | Data Centers